MSI-RM2B-02 Leuze Safety Relays
Part#:MSI-RM2B-02
Manufacturer:Leuze
Alt. Part#:547955
Product Lifecycle:Active
Get a quick Quote!
MSI-RM2B-02 Leuze - Safety relay
Check out the MSI-RM2B-02 Leuze price in the box on the right side or send a quick quote.
Product Details
- Customs tariff number 85371098
- Ambient temperature, storage -25 ... 70 °C
- Number of LEDs 2 Piece(s)
- Approvals TÜV NRTL US; c UL US
- Ambient temperature, operation 0 ... 50 °C
- Protection class II
- Degree of protection IP 20
- Mechanical life time 10,000,000 actuation cycles
- Type of display LED
- Housing color Gray
- Type of fastening Snap-on mounting
- Net weight 120 g
- Electrical contact material AgNi10 + 5 mm Au
- Connection cross sections 0.2 to 1.5 mm²
- Housing material Plastic
- Dimension (W x H x L) 17.5 mm x 111 mm x 114.1 mm
- No. of pins 12 -pin
- Plastic housing PA 66
- Type of terminal Spring-cage terminal
- Function Connection to device
- Number of outputs, safety-oriented, non-delayed, contact-based 2 Piece(s)
- Number of outputs, signaling function, non-delayed, contact-based 1 Piece(s)
- Pickup delay 20 ms
- Type of connection Terminal
- Number of connections 1 Piece(s)
- Number of outputs, safety-oriented, delayed, contact-based 0 Piece(s)
- Regression delay 10 ms
- Power consumption, max. 2.5 W, For 24 V, plus output load
- Voltage type AC/DC
- Switching element Relay, NO
- Supply voltage UB 24 V, DC, -20 ... 20 %
- Protective circuit Fuse on switching output, upstream
- External contact fuse protection per current path 5 A quick-action, or 3.15 A delay-action
- Type Safety-related switching output OSSD
- Permissible input line resistance, max. 50 Ω
- Switching frequency, max. 36000 switching cycles/h
- Continuous current per current path, max. 3 A
- Number of safety-related switching outputs (OSSDs) 2 Piece(s)
- B10d at AC15 (inductive load) 1,300,000 number of cycles, (0.5 A, 230 V)
- B10d, low load 1,860,000 number of cycles
- B10d at AC1 (ohmic load) 1,300,000 number of cycles, (0.5 A, 230 V)
- B10d at DC13 (inductive load) 10,000,000 number of cycles, (2 A, 24 V)
- B10d at DC1 (ohmic load) 10,000,000 number of cycles, (2 A, 24 V)
- Category Up to 4 (depending on the category of the upstream protective device), EN ISO 13849-1
- SILCL 3, IEC/EN 62061
- Functions Feedback path for EDM integration
- Mission time 20 years, EN ISO 13849-1
- Application Signal conversion of electronic safety outputs on potential-free relay contacts
- Restart Automatic
- Series MSI-RM2B
- Performance Level (PL) e, EN ISO 13849-1
- SIL 3, IEC 61508
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
MSI-RM2B-02 Description
MSI-RM2B-02 Leuze - Safety relay
Related documents MSI-RM2B-02 Specs
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Leuze
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Leuze Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Leuze Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Leuze, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨