MSI-SR-LC21-03 Leuze Safety Relays
Part#:MSI-SR-LC21-03
Manufacturer:Leuze
Alt. Part#:50133009
Product Lifecycle:Active
Get a quick Quote!
MSI-SR-LC21-03 Leuze - Safety relay
Check out the MSI-SR-LC21-03 Leuze price in the box on the right side or send a quick quote.
Product Details
- Approvals TÜV Rheinland; c UL US
- Customs tariff number 85364900
- Ambient temperature, operation -25 ... 55 °C
- Type of fastening Snap-on mounting
- Net weight 210 g
- Housing color Gray
- Connection cross sections 2 x 0.2 to 1.5 mm², wire; 2 x 0.25 to 1.5 mm², wire with wire-end sleeve
- Type of connection Terminal
- No. of pins 16 -pin
- Dimension (W x H x L) 22.5 mm x 106.5 mm x 114 mm
- Function Signal IN; Signal OUT; Voltage supply
- Type of terminal Spring-cage terminal
- Number of connections 1 Piece(s)
- Regression delay 25 ms
- Minimum switch-on time 50 ms
- Recovery time tW 150 ms
- Release time tR 25 ms
- Synchronous time monitoring tS 200 ms
- Test pulse time permitted tTP 1 ms
- Response time (manual start tA1) 40 ms
- Input current at the control inputs (safety circuit/reset circuit) 40 mA
- Response time (automatic start tA2) 500 ms
- Max. cable resistance, per channel ≤ (5 + (1.176 x UB / UN - 1) x 100) Ω
- Max. peak current at the control inputs (safety circuit/reset circuit) 100 mA
- Max. thermal continuous current Ith, release current paths 6 A
- Max. total current I² of all current paths 9 A²
- Short circuit protection (NO contact) gG class safety fuse 6A, melting integral
- Usage category AC-15 (NO contact) Ue 230V, Ie 3A
- Max. thermal continuous current Ith, signaling current paths 3 A
- Usage category DC-13 (NO contact) Ue 24V, Ie 2,5A
- Contact material Ag alloy, gold-plated
- Evaluation of the inputs Two-channel
- Mechanical life time 100,000,000 switching cycles
- Number of outputs, signaling function, non-delayed, contact-based 1 Piece(s)
- Release current paths NO
- Galvanic isolation between supply and control circuit No
- Signaling current paths NC
- Number of outputs, safety-oriented, delayed, contact-based 0 Piece(s)
- Number of outputs, safety-oriented, non-delayed, contact-based 2 Piece(s)
- Rated power DC 2 W
- Power consumption, max. 2 W, For 24 V, plus output load
- Operating voltage 0.85 ... 1.1 x UN
- Nominal voltage UN 24 V
- Nominal frequency 50 ... 60 Hz
- Supply voltage UB 24 V, AC/DC, -15 ... 10 %
- Continuous current per current path, max. 6 A
- Mission time 20 years, EN ISO 13849-1
- Category 4, EN ISO 13849-1
- DCAVG 99 %
- B10d at DC13 (inductive load) 435,000 number of cycles, (2.5 A, 230 V), 700,000 (1 A, 230 V)
- B10d at AC15 (inductive load) 230,000 number of cycles, (3 A, 230 V), 380,000 (1 A, 230 V)
- MTTFd 78 years, EN ISO 13849-1
- PFHD 1,7E-09 per hour
- Functions Contactor monitoring (EDM); Start/restart interlock (RES)
- SILCL 3, IEC/EN 62061
- Performance Level (PL) e, EN ISO 13849-1
- Application E-Stop circuits; Optoelectronic protective devices; Position switches (mechanical contacts); Solenoid switches (reed contacts, equivalent); Transponder switches (OSSD outputs)
- Series MSI-SR-LC21
- Restart Automatic; Manual
- SIL 3, IEC 61508
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
MSI-SR-LC21-03 Description
MSI-SR-LC21-03 Leuze - Safety relay
Related documents MSI-SR-LC21-03 Specs
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Leuze
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Leuze Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Leuze Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Leuze, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨