1104889 Phoenix Contact Electrical Safety Devices
Part#:1104889
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 50
Dec 22, 2024
Safe extension module with 8 safe inputs and 4 safe outputs, 4 reset inputs or 4 signal outputs, 4 clock outputs, TBUS interface, up to SILCL 3, Cat. 4/PL e, SIL 3, pluggable Push-in terminal block, TBUS connector included
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 1104889 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Width 22.61 mm
- Max. permissible relative humidity (operation) 95 % (non-condensing)
- Indication 2 x LED (red)
- Ambient temperature (storage/transport) -20 °C ... 85 °C
- Maximum altitude ≤ 2000 m (Above sea level)
- Protective circuit Serial protection against polarity reversal
- Input voltage range "1" signal 11 V DC ... 28.8 V DC
- Number of outputs 4
- Nominal output voltage range 18.5 V DC ... 28.1 V DC (US - 0,7 V)
- Output voltage when switched off max. 0.1 V
- Discharging circuit Yes, internal
- Maximum inrush current 1.1 A (Δt = 3 s at Us)
- Response time see user manual
- Nominal operating mode 100% operating factor
- Protection class III (EN 50178)
- Depth 113.6 mm
- Designation Air clearances and creepage distances between the power circuits
- Current consumption typ. 12 mA (typically with US)
- Description of the input configurable (as signal output or reset input)
- Max. permissible overall conductor resistance 1.2 kΩ (Input and reset circuit at US)
- Output name O1, O2, O3, O4
- Leakage current max. 100 µA
- Switching frequency max. 1/4 x tCycle [Hz]
- Conductor cross-section AWG 24 ... 16
- Performance level (PL) e (2-channel wiring)
- Standards/regulations EN 50178
- Degree of pollution 2
- ECLASS 9.0 27371819
- Ambient temperature (operation) -10 °C ... 55 °C (observe derating)
- Power consumption at US typ. 1.08 W (Outputs inactive)
- Input voltage range "0" signal 0 V DC ... 5 V DC
- Cable length max. 100 m (per output)
- Nominal output voltage 24 V DC (Supply via A1)
- Max. capacitive load max. 470 nF
- Test pulses ≤ 200 µs (Test pulse duration)
- Voltage 24 V DC (via A1)
- Nominal voltage range 18.2 V DC ... 27.8 V DC (US - 1 V)
- Mounting type DIN rail mounting
- Assembly instructions Observe derating
- Housing material Polyamide PA non-reinforced
- Status display 1 x LED (green), 2 x LED (orange)
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Rated insulation voltage 250 V AC
- China RoHS Environmentally friendly use period: unlimited = EFUP-e
- Conformance CE-compliant
- Height 107.74 mm
- Max. permissible humidity (storage/transport) 95 % (non-condensing)
- Rated control supply current IS typ. 45 mA (Outputs inactive)
- Inrush current max. 600 mA (Δt < 10 ms)
- Number of inputs 4
- Input current range "0" signal < 1 mA
- Protective circuit/component Suppressor diode
- Ohmic load min. 50 Ω (Observe limiting continuous current)
- Short-circuit protection Yes (self-limitation at 1.1 A)
- Cycle time see user manual
- Net weight 141 g
- Degree of protection IP20
- Housing color yellow
- Connection method Push-in connection
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Safety Integrity Level Claim Limit (SIL CL) 3 (2-channel wiring)
- Vibration (operation) 10 Hz ... 150 Hz, 2g
- ECLASS 11.0 27371819
- Rated control circuit supply voltage US 24 V DC -20 % / +20 % (external fuse, typically 4 A)
- Filter time 250 ms ±2 ms (Test pulse rate > 500 ms)
- Input name Reset inputs
- Output description PNP, IEC 61131-2 Typ 0,1
- Limiting continuous current 100 mA (per channel)
- Max. inductive load max. 2.4 mH
- Error detection time at 1-channel structure < 3.5 s (OFF state)
- Output voltage range 18.2 V DC ... 27.8 V DC (US - 1 V)
- Restart time min. 5 s (Boot time)
- Mounting position vertical or horizontal
- Min. degree of protection of inst. location IP54
- Operating voltage display 1 x green LED
- pluggable Yes
- Stripping length 10 mm
- Stop category 0
- Rated surge voltage/insulation Basic insulation 4 kV between 24 V power supply and I/Os to the housing
- Overvoltage category II
- Safety Integrity Level (SIL) 2
- Shock 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction)
- ECLASS 10.0.1 27371819
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 5 days!
1-year warranty
$548.13
Stock:
50
Select Qty:
$548.13
$548.13 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.