2986960 Phoenix Contact Electrical Safety Devices
Part#:2986960
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 356
Dec 22, 2024
Safe coupling relay for SIL 3 high and low demand applications, connects digital output signals to the I/O, 2 enabling current paths, 1 signal contact, module for safe state off applications, integrated test pulse filter, plug-in screw connection, width:
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2986960 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Width 17.5 mm
- Ambient temperature (storage/transport) -40 °C ... 70 °C
- Inrush current max. 100 mA
- Filter time max. 5 ms (at A1 in the event of voltage dips at Us)
- Inrush current, minimum 5 mA (N/O contact / N/C contact)
- Mechanical service life 10x 106 cycles
- Mounting type DIN rail mounting
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Safety Integrity Level (SIL) 3
- Rated insulation voltage 250 V
- Rated surge voltage/insulation Safe isolation, reinforced insulation 6 kV between the control circuits (A1/A2), (31/32), (13/14, 23/24)
- REACh SVHC Lead 7439-92-1
- China RoHS Environmentally Friendly Use Period = 50 years
- ECLASS 7.0 27371819
- ETIM 3.0 EC001449
- ETIM 4.0 EC001449
- ETIM 7.0 EC001449
- UNSPSC 21.0 39122205
- Depth 114.5 mm
- Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
- Protective circuit Surge protection Suppressor diode, 33 V (A1 - A2)
- Contact material AgCuNi, + 0.2 µm Au
- Interrupting rating (ohmic load) max. 120 W (24 V DC, τ = 0 ms, N/C contact: 2.4 W)
- Nominal operating mode 100% operating factor
- pluggable Yes
- Stop category 0
- Designation Air clearances and creepage distances between the power circuits
- Standards/regulations DIN EN 50178/VDE 0160
- Vibration (operation) 10 Hz ... 150 Hz, 2g
- ECLASS 4.0 40020600
- ECLASS 5.1 27371900
- ECLASS 9.0 27371819
- UNSPSC 7.0901 39121501
- UNSPSC 18.0 39122205
- Ambient temperature (operation) -20 °C ... 55 °C (observe derating)
- Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
- Input voltage range 20.4 V DC ... 26.4 V DC
- Typ. starting time with Us 50 ms
- Operating voltage display 1 x yellow LED
- Maximum switching frequency 0.5 Hz
- Maximum inrush current 5 A (N/O contact)
- Sq. Total current 50 A2 (observe derating)
- Output fuse 10 A gL/gG (N/O contact)
- Relay type Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
- Min. degree of protection of inst. location IP54
- Housing material PBT
- Stripping length 7 mm
- Safety Integrity Level Claim Limit (SIL CL) 3 (max. 10% of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90% )
- Overvoltage category III
- Conformance CE-compliant
- ECLASS 4.1 40020600
- ECLASS 5.0 27371900
- ECLASS 6.0 27371800
- UNSPSC 6.01 30211901
- UNSPSC 12.01 39121501
- UNSPSC 20.0 39122205
- Height 99 mm
- Maximum altitude ≤ 2000 m (Above sea level)
- Power consumption at US typ. 1.32 W
- Typical release time 50 ms
- Contact type 2 enabling current paths
- Limiting continuous current 5 A (N/O contact, pay attention to the derating)
- Switching capacity min. 75 mW
- Net weight 155 g
- Degree of protection IP20
- Housing color yellow
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Performance level (PL) e (Diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 99%)
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Rated control circuit supply voltage US 24 V DC -15 % / +10 %
- Rated control supply current IS typ. 55 mA
- Recovery time 1 s
- Maximum switching voltage 250 V AC/DC (N/O contact / N/C contact, observe the load curve)
- Minimum switching voltage 15 V AC/DC (N/O contact / N/C contact)
- Maximum interrupting rating (inductive load) 72 W (24 V DC, τ = 40 ms, N/C contact: 2.4 W)
- Mounting position any
- Connection method Screw connection
- Conductor cross-section AWG 24 ... 12
- Screw thread M3
- Category 4 (Diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 99%)
- Degree of pollution 2
- Shock 15g
- ECLASS 10.0.1 27371819
- ECLASS 11.0 27371819
- ETIM 2.0 EC001449
- ETIM 6.0 EC001449
- UNSPSC 11 39121501
- UNSPSC 13.2 39121501
- UNSPSC 19.0 39122205
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$282.73
Stock:
356
Select Qty:
$282.73
$282.73 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨