Fuse modular terminal block, fuse type: Glass / ceramics / ..., number of positions: 1, connection method: Screw connection, cross section: 0.2 mm²- 4 mm², AWG: 24 - 12, nominal current: 6.3 A, nom. voltage: 800 V, width: 8.2 mm, fuse type: G / 5 x 20 / 5
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 3004100 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Note Swing the locking lever to its final position before replacing the fuse.
- Color black
- Rated surge voltage 8 kV
- Maximum load current 6.3 A (the current is determined by the fuse used)
- Fuse G / 5 x 20 / 5 x 25 / 5 x 30
- Back of the hand protection guaranteed
- Result of power-frequency withstand voltage test Test passed
- Compatibitity between modular fuse terminal block and fuse insert Test passed
- Bending test conductor cross section/weight 0.2 mm² / 0.2 kg
- Bending test turns 135
- Result of thermal test Test passed
- Acceleration 5g
- Relative insulation material temperature index (Elec., UL 746 B) 130 °C
- Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
- Number of shocks per direction 3
- Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
- Height NS 32 61.5 mm
- Conductor cross section flexible, with ferrule without plastic sleeve max. 4 mm²
- Conductor cross section AWG max. 12
- 2 conductors with same cross section, solid min. 0.2 mm²
- Stripping length 8 mm
- Tightening torque, min 0.6 Nm
- Ambient temperature (actuation) -5 °C ... 70 °C
- ECLASS 5.0 27141100
- ETIM 2.0 EC000897
- ETIM 7.0 EC000899
- Insulating material group I
- Nominal current IN 6.3 A
- Open side panel No
- Result of surge voltage test Test passed
- Power frequency withstand voltage setpoint 2 kV
- Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
- Conductor cross section flexible, with ferrule with plastic sleeve max. 4 mm²
- 2 conductors with same cross section, stranded max. 1.5 mm²
- Internal cylindrical gage A4
- Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 125°C)
- ECLASS 10.0.1 27141116
- ECLASS 6.0 27141100
- ETIM 6.0 EC000899
- UNSPSC 6.01 30211811
- UNSPSC 18.0 39121410
- Maximum power dissipation for nominal condition 1.02 W
- Connection in acc. with standard CSA
- Fuse type Glass / ceramics / ...
- Finger protection guaranteed
- Result of tight fit on support Test passed
- Contact resistance Test passed
- Result of temperature-rise test Test passed
- Test spectrum Service life test category 1, class B, body mounted
- Test directions X-, Y- and Z-axis (pos. and neg.)
- ASD level 1.857 (m/s2)2/Hz
- Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
- Static insulating material application in cold -60 °C
- Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
- Width 8.2 mm
- Height NS 35/15 64 mm
- Conductor cross section flexible max. 4 mm²
- Conductor cross section flexible, with ferrule with plastic sleeve min. 0.25 mm²
- 2 conductors with same cross section, solid max. 1.5 mm²
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 1.5 mm²
- Permissible humidity (storage/transport) 30 % ... 70 %
- ECLASS 4.0 27141100
- ECLASS 4.1 27141100
- ECLASS 7.0 27141116
- UNSPSC 12.01 39121410
- UNSPSC 20.0 39121410
- Insulating material PA
- Overvoltage category III
- Number of positions 1
- Surge voltage test setpoint 9.8 kV
- Actuatiing forces on plug in or lever in fuse insert carriers Test passed
- Result of flexion and pull-out test Test passed
- Testing the rated value of the power dissipation (exclusively short circuit protection) Test passed
- Testing the rated value of the power dissipation (overload and short circuit Protection) Test passed
- Test frequency f1 = 5 Hz to f2 = 150 Hz
- Test duration per axis 5 h
- Shock form Half-sine
- Surface flammability NFPA 130 (ASTM E 162) passed
- Smoke gas toxicity NFPA 130 (SMP 800C) passed
- Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section flexible min. 0.2 mm²
- Cross section with insertion bridge, solid max. 4 mm²
- 2 conductors with same cross section, stranded min. 0.2 mm²
- Connection method Screw connection
- Tightening torque max 0.8 Nm
- Ambient temperature (assembly) -5 °C ... 70 °C
- ECLASS 9.0 27141116
- ETIM 3.0 EC000899
- UNSPSC 7.0901 39121410
- UNSPSC 19.0 39121410
- Shock test result Test passed
- Shock duration 30 ms
- Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
- Specific optical density of smoke NFPA 130 (ASTM E 662) passed
- Length 72.5 mm
- Conductor cross section solid max. 4 mm²
- Conductor cross section AWG min. 24
- Cross section with insertion bridge, stranded max. 4 mm²
- Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum 0.5 mm²
- Screw thread M3
- Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
- ECLASS 11.0 27141116
- ECLASS 5.1 27141100
- ETIM 4.0 EC000899
- UNSPSC 13.2 39121410
- UNSPSC 21.0 39121410
- Number of levels 1
- Rated operating voltage 250 V
- Degree of pollution 3
- Flammability rating according to UL 94 V0
- Conductor cross section flexible, with ferrule without plastic sleeve min. 0.25 mm²
- Height NS 35/7,5 56.5 mm
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum 0.25 mm²
- China RoHS Environmentally Friendly Use Period = 50 years
- Number of connections 2
- Nominal cross section 4 mm²
- Nominal voltage UN 800 V (As a fuse terminal block)
- Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
- UNSPSC 11 39121410
- Bending test rotation speed 10 rpm
- Oscillation, broadband noise test result Test passed
- Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2008-03
- Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum 1.5 mm²
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$14.94
Stock:
7,745
Select Qty:
$14.94
$14.94 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨