X67AT1402 B&R Electronic Components

B&R X67AT1402 X67 temperature input module, 4 thermocouple inputs, type J, K, N, R, S, resolution 0.1 K
B&R

Part#:X67AT1402

Manufacturer:B&R

Product Lifecycle:Active

In-stock parts: 1

Dec 22, 2024

X67 temperature input module, 4 thermocouple inputs, type J, K, N, R, S, resolution 0.1 K

Check out the X67AT1402 B&R price in the box on the right side or send a quick quote.

Product Details

  • Weight205 g
  • Max. error at 25°C Offset Type R: PtRh13-Pt
    ±0.078%
  • Max. error at 25°C Offset Type N: NiCrSi-NiSi
    ±0.035%
  • Max. error at 25°C Offset Type S: PtRh10-Pt
    ±0.088%
  • Max. error at 25°C Offset Type T: Cu-CuNi
    ±0.024%
  • Max. error at 25°C Offset Type K: NiCr-Ni
    ±0.030%
  • Measurement range Sensor temperature Type R: PtRh13-Pt
    -50 to 1768°C
  • Measurement range Sensor temperature Type S: PtRh10-Pt
    -50 to 1768°C
  • Dimensions Depth
    42 mm
  • Measurement range Sensor temperature Type K: NiCr-Ni
    -270 to 1372°C
  • Measurement range Sensor temperature Type J: Fe-CuNi
    -210 to 1200°C
  • Measurement range Sensor temperature Type N: NiCrSi-NiSi
    -270 to 1300°C
  • Torque for connections M12
    Max. 0.6 Nm
  • Torque for connections M8
    Max. 0.4 Nm
  • Dimensions Width
    53 mm
  • Dimensions Height
    85 mm
  • Temperature Transport
    -40 to 85°C
  • Temperature Storage
    -40 to 85°C
  • Temperature Operation
    -25 to 60°C
  • Installation elevation above sea level 0 to 2000 m
    No limitation
  • Input filter Slope
    -20 dB
  • Temperature Derating
    -
  • Installation elevation above sea level >2000 m
    Reduction of ambient temperature by 0.5°C per 100 m
  • Mounting orientation Any
    Yes
  • Common-mode rejection 50 Hz
    >70 dB
  • Common-mode rejection DC
    >70 dB
  • Input filter Cutoff frequency
    4 Hz / First-order filter
  • Max. offset drift Type R: PtRh13-Pt
    0.0079%/°C
  • Max. offset drift Type S: PtRh10-Pt
    0.0089%/°C
  • Max. offset drift Type N: NiCrSi-NiSi
    0.0035%/°C
  • Max. offset drift Type J: Fe-CuNi
    0.0024%/°C
  • Monitoring Open circuit
    0x7FFF
  • Monitoring General fault
    0x8000
  • Max. offset drift Type K: NiCr-Ni
    0.0030%/°C
  • Max. error at 25°C Gain
    ±0.040%
  • Monitoring Open inputs
    0x7FFF
  • Monitoring Range undershoot
    0x8001
  • Monitoring Range overshoot
    0x7FFF
  • Normalization Type R: PtRh13-Pt
    -50.0 to 1768.0°C
  • Normalization Type S: PtRh10-Pt
    -50.0 to 1768.0°C
  • Normalization Type N: NiCrSi-NiSi
    -270.0 to 1300.0°C
  • Normalization Type J: Fe-CuNi
    -210.0 to 1200.0°C
  • Resolution Raw value output with respect to gain
    1 LSB = 1 µV or 2 µV
  • Resolution Terminal temperature
    1 LSB = 0.1°C
  • Normalization Type K: NiCr-Ni
    -270.0 to 1372.0°C
  • Measurement range Terminal temperature
    -25 to 85°C
  • Resolution Sensor temperature
    1 LSB = 0.1°C
  • Measurement range Raw value
    ±65.534 mV
  • Certifications KC
    Yes
  • Certifications EAC
    Yes
  • Certifications ATEX
    Zone 2, II 3G Ex nA IIA T5 Gc; IP67, Ta = 0 - Max. 60°C; TÜV 05 ATEX 7201X
  • Certifications CE
    Yes
  • Certifications UKCA
    Yes
  • Certifications HazLoc
    cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
  • Certifications UL
    cULus E115267; Industrial control equipment
  • Power consumption X2X Link power supply
    0.75 W
  • Power consumption Internal I/O
    2.6 W
  • Connection type X2X Link
    M12, B-coded
  • Connection type I/O power supply
    M8, 4-pin
  • Connection type Inputs
    4x M12, A-coded
  • Electrical isolation
    Channel isolated from bus; Channel not isolated from channel
  • Terminal temperature error
    Typ. ±2°C after 10 min.
  • Insulation voltage between channel and bus
    500 Veff
  • Diagnostics Inputs
    Yes, using LED status indicator and software
  • Diagnostics I/O power supply
    Yes, using LED status indicator and software
  • Degree of protection per EN 60529
    IP67
  • Crosstalk between channels
    <-70 dB
  • Conversion time
    62 ms per channel with 50 Hz filter + 62 ms per cycle for terminal temperature measurement with 50 Hz filter
  • Common-mode range
    ±12 VDC
  • Linearization method
    Software
  • Nonlinearity
    <0.002%
  • Max. gain drift
    0.0123%/°C
  • Permissible input signal
    Short-term ±30 VDC
  • Terminal temperature compensation
    Using thermocouple connector X67AC9A02 (accessory)
  • Conversion procedure
    Sigma-delta
  • Sensor standard
    IEC 60584-1
  • Output format
    INT
  • Voltage range
    18 to 30 VDC
  • Digital converter resolution
    16-bit
  • Integrated protection
    Reverse polarity protection
  • Input
    Thermocouple
  • I/O module
    4 inputs for thermocouple sensors
  • Status indicators
    I/O function per channel, supply voltage, bus function
  • Nominal voltage
    24 VDC
  • B&R ID code
    0x1486
  • Filter time
    Configurable between 2 and 20 ms

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



1-year warranty

Get a quick Quote!

Request a quote, and we will send you price within minutes.

Stock:

1

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of B&R

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

B&R Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many B&R Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from B&R, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo