1190012 Phoenix Contact Programmable Logic Controllers
Part#:1190012
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 2
Dec 26, 2024
Axioline Smart Elements, Digital input module, SafetyBridge technology, Safe digital inputs: 8 (1-channel assignment), 4 (2-channel assignment), 24 V DC, connection method: 3-conductor, degree of protection: IP20
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Programmable Logic Controllers that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 1190012 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 62.2 mm
- Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
- Degree of protection IP20
- Conductor cross section solid max. 1.5 mm²
- Conductor cross section AWG min. 24
- Cable length max. 200 m (200 m from the clock output to the safe input (total based on forward and return path))
- Nominal voltage UN 24 V DC (from UP)
- Short-circuit protection Yes
- Mounting position any
- Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
- Category 3 (1-channel assignment)
- Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, 2 kV
- Protection class III (IEC 61140, EN 61140, VDE 0140-1)
- ECLASS 9.0 27242604
- Caption Dimensions
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Air pressure (storage/transport) 66 kPa ... 108 kPa
- Designation EN 62061
- Number 1
- Connection technology 3-conductor
- Number of inputs 8 (1-channel assignment)
- Input current range "0" signal max. 1.5 mA
- Limiting continuous current max. 0.5 A DC (per clock output)
- Operating mode SafetyBridge
- Maximum altitude ≤ 3000 m (Above sea level)
- Protection external fusing via the system in which the Smart Element is used
- Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Test intensity 2, Criterion APower supply: 0.5 kV/0.5 kV (symmetrical/unsymmetrical)Signal lines: 1.0 kV/2.0 kV (symmetrical/unsymmetrical)
- Overvoltage category II (IEC 60664-1)
- Depth 62 mm
- Air pressure (operation) 70 kPa ... 108 kPa
- Note on the connection method Note the specification in the section Conductor cross sections, and stripping and insertion lengths.
- Conductor cross section AWG max. 16
- Transmission speed See system in which you use the Smart Element.
- Protective circuit Surge protection of the supply voltage electronic (35 V, 0.5 s)
- Nominal input current at UIN typ. 2.7 mA
- Input current range “1“ signal min. 2 mA
- Mounting type Smart Element slot
- Net weight 36 g
- Power consumption min. 154 mW
- Performance level (PL) d (1-channel assignment)
- Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
- Air clearances and creepage distances IEC 60664-1
- ECLASS 10.0.1 27242604
- Width 14.9 mm
- Permissible humidity (operation) 5 % ... 95 % (non-condensing)
- Connection method Push-in connection
- Conductor cross section solid min. 0.25 mm²
- Conductor cross section flexible min. 0.25 mm²
- Description of the input EN 61131-2, type 3
- Nominal input voltage UIN 24 V DC
- Input filter time 1.5 ms
- Input voltage range "1" signal 11 V DC ... 30 V DC
- Switching frequency max. 10 Hz
- Degree of pollution 2 (EN 60664-1)
- Current consumption min. 8 mA (Power supply from Up with 19.2 V DC, all inputs set, without power supply to the sensors via clock supplies OUT_T1 and OUT_T2)
- Safety Integrity Level Claim Limit (SIL CL) 2 (1-channel assignment)
- Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion A, 6 kV contact discharge, 8 kV air discharge
- Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
- ECLASS 11.0 27242604
- Conductor cross section flexible max. 1.5 mm²
- Stripping length 8 mm
- Input voltage range "0" signal -3 V DC ... 5 V DC
- Ambient temperature (operation) -25 °C ... 60 °C
- Degree of protection at installation location min. IP54
- Input name Safe digital inputs
- Number of outputs 2
- Color zinc yellow RAL 1018
- Supply voltage 24 V DC (using card edge connectors)
- Additional text using card edge connectors
- Safety Integrity Level (SIL) 2 (1-channel assignment)
- Interference emission Noise emission test as per EN 61000-6-4 Class A (industrial applications)
- Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$282.41
Stock:
2
Select Qty:
$282.41
$282.41 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.