Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 3-phase, output: 24 V DC/20 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2903155 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 130 mm
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Nominal input voltage range 3x 400 V AC ... 500 V AC
- Discharge current to PE < 3.5 mA
- Mains buffering time typ. 10 ms (400 V AC)
- Depth 160 mm
- Degree of protection IP20
- Ambient temperature (start-up type tested) -40 °C
- Climatic class 3K3 (in acc. with EN 60721)
- Input voltage range 3x 400 V AC ... 500 V AC -20 % ....+15 %
- Current consumption 3x 1.2 A (400 V AC)
- Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
- Nominal output current (IN) 20 A
- Connection in series yes
- Output power 480 W
- Power loss nominal load max. < 38 W (480 V AC)
- Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section flexible max. 1.5 mm²
- Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
- Shipbuilding approval GL applied for
- Noise emission EN 55016
- Electromagnetic HF field EN 61000-4-3
- Fast transients (burst) EN 61000-4-4
- Output 1 kV (Test Level 2 - symmetrical)
- Number of periods 1 period
- Additional text Test Level 2
- China RoHS Environmentally Friendly Use Period = 25;
- Conductor cross section AWG min. 24
- EMC requirements for noise emission EN 61000-6-3
- Rail applications EN 50121-4
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Input 3 kV (Test Level 3 - symmetrical)
- Voltage 230 V AC
- Criterion A Normal operating behavior within the specified limits.
- REACh SVHC Lead 7439-92-1
- ECLASS 4.0 27040700
- ECLASS 4.1 27040700
- UNSPSC 21.0 39121004
- Installation distance top/bottom 50 mm / 50 mm
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Installation height ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
- Inrush current ≤ 22 A (typical)
- Power factor (cos phi) 0.63
- Nominal output voltage 24 V DC ±1 %
- Connection in parallel Yes, for redundancy and increased capacity
- Residual ripple ≤ 20 mVPP
- MTBF (IEC 61709, SN 29500) > 1800000 h (25 °C)
- Protection class I (in closed control cabinet)
- Connection method Push-in connection
- EMC requirements for noise immunity EN 61000-6-1
- Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
- Conducted noise emission EN 55016
- Electrostatic discharge EN 61000-4-2
- Frequency range 0.15 MHz ... 80 MHz
- Conducted interference EN 61000-4-6
- Voltage dip 0 %
- ECLASS 11.0 27040701
- ECLASS 6.0 27049000
- ECLASS 9.0 27040701
- UNSPSC 13.2 39121004
- Width 65 mm
- Installation distance right/left 0 mm / 0 mm
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Degree of pollution 2
- AC frequency range 50 Hz ... 60 Hz
- Nominal power consumption 822.2 VA
- Input fuse 3.15 A (internal (device protection), slow-blow)
- Protective circuit/component Varistor
- Dynamic Boost (IDyn.Boost) 30 A (5 s)
- Control deviation < 1 % (change in load, static 10 % ... 90 %)
- Maximum power dissipation in no-load condition < 1.2 W (400 V AC)
- Net weight 1.5 kg
- Insulation voltage input/output 3 kV AC (type test)
- Conductor cross section flexible min. 0.2 mm²
- Conductor cross section AWG max. 16
- Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
- Standard - Safe isolation DIN VDE 0100-410
- Discharge in air 8 kV (Test Level 4)
- Comments Criterion A
- Signal 1 kV (Test Level 1 - asymmetrical)
- Voltage dips EN 61000-4-11
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- ECLASS 5.1 27049000
- ETIM 4.0 EC002540
- ETIM 7.0 EC002540
- Type of protection Transient surge protection
- Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
- Derating > 60 °C ... 70 °C (2.5%/K)
- Protection against overvoltage at the output (OVP) ≤ 30 V DC
- Typical response time < 1 s
- Efficiency > 93 % (400 V AC)
- Mounting position horizontal DIN rail NS 35, EN 60715
- Conductor cross section solid max. 1.5 mm²
- Stripping length 8 mm
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
- Standard – Limitation of mains harmonic currents EN 61000-3-2
- UL approvals UL Listed UL 508
- Contact discharge 6 kV (Test Level 4)
- Test field strength 10 V/m (Test Level 3)
- Surge voltage load (surge) EN 61000-4-5
- Frequency 50 Hz
- ECLASS 10.0.1 27040701
- ECLASS 5.0 27049000
- ETIM 6.0 EC002540
- UNSPSC 18.0 39121004
- UNSPSC 20.0 39121004
- ECLASS 7.0 27049002
- UNSPSC 19.0 39121004
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 5 days!
1-year warranty
$335.54
Stock:
15
Select Qty:
$335.54
$335.54 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨