Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

LC1D806BD Schneider Electric Industrial Automation Components

Schneider Electric LC1D806BD Schneider Electric LC1D806BD is a magnetic contactor from the Deca sub-range, designed for ring-lugs connections. It features 3 poles (3P; 3NO) and is rated for a current of 125A (AC-1) and 80A (440Vac; AC-3). This contactor is suitable for DIN rail mounting and has a net width of 85 mm. It offers a degree of protection of IP20 and operates with a control voltage (DC) of 20.4-26.4Vdc (24Vdc nom.; 0.85...1.1 x Uc). The rated operating voltage (Ue) is 1000 V, and it includes 1 normally open (NO) auxiliary contact. The rated impulse voltage (Uimp) is 8 kV. Its rated active power ranges from 22kW (220-230Vac; AC-3) to 55kW (500Vac; AC-3), with specific ratings for various voltages up to 1000Vac. It also features 1 normally closed (NC) auxiliary contact and instantaneous auxiliary contacts type of 1NO+1NC. The rated power in horsepower (HP) varies from 7.5HP at 115Vac single-phase to 60HP at 575-600Vac 3-phase. The mechanical durability of the LC1D806BD is rated at 4,000,000 operations, and its electrical durability with load is 1,500,000 operations. The rated voltage (AC) phase-to-phase is 1000 V.
Schneider Electric

Part#:LC1D806BD

Manufacturer:Schneider Electric

Product Lifecycle:Active

Get a quick Quote!

Schneider Electric LC1D806BD is a magnetic contactor from the Deca sub-range, designed for ring-lugs connections. It features 3 poles (3P; 3NO) and is rated for a current of 125A (AC-1) and 80A (440Vac; AC-3). This contactor is suitable for DIN rail mounting and has a net width of 85 mm. It offers a degree of protection of IP20 and operates with a control voltage (DC) of 20.4-26.4Vdc (24Vdc nom.; 0.85...1.1 x Uc). The rated operating voltage (Ue) is 1000 V, and it includes 1 normally open (NO) auxiliary contact. The rated impulse voltage (Uimp) is 8 kV. Its rated active power ranges from 22kW (220-230Vac; AC-3) to 55kW (500Vac; AC-3), with specific ratings for various voltages up to 1000Vac. It also features 1 normally closed (NC) auxiliary contact and instantaneous auxiliary contacts type of 1NO+1NC. The rated power in horsepower (HP) varies from 7.5HP at 115Vac single-phase to 60HP at 575-600Vac 3-phase. The mechanical durability of the LC1D806BD is rated at 4,000,000 operations, and its electrical durability with load is 1,500,000 operations. The rated voltage (AC) phase-to-phase is 1000 V.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at marketplace.quotebeam.com. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1D806BD Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Product Certifications
    LROS (Lloyds register of shipping) CCC DNV GL GOST RINA BV UL CSA
  • Motor Power Kw
    22 kW 220...230 V AC 50/60 Hz AC-3) 37 kW 380...400 V AC 50/60 Hz AC-3) 45 kW 415...440 V AC 50/60 Hz AC-3) 55 kW 500 V AC 50/60 Hz AC-3) 45 kW 660...690 V AC 50/60 Hz AC-3) 45 kW 1000 V AC 50/60 Hz AC-3) 15 kW 400 V AC 50/60
  • Motor Power HP (UL / CSA)
    20 hp 200/208 V at AC 50/60 Hz for 3 phase 7.5 hp 115 V at AC 50/60 Hz for 1 phase 15 hp 230/240 V at AC 50/60 Hz for 1 phase 25 hp 230/240 V at AC 50/60 Hz for 3 phase 60 hp 460/480 V at AC 50/60 Hz for 3 phase 60 hp 575/600 V at
  • [Icw] Rated Short-Time Withstand Current
    640 A 104 °F (40 °C) - 10 s power circuit 990 A 104 °F (40 °C) - 1 s power circuit 135 A 104 °F (40 °C) - 10 min power circuit 320 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling cir
  • [Ui] Rated Insulation Voltage
    Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
  • Standards
    CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • Tightening Torque
    Control circuit 10.62 lbf.in (1.2 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 10.62 lbf.in (1.2 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 106.21 lbf.in (12 N.m) lugs-ring terminals flat Ø 8 mm M6 Power circuit 1
  • Irms Rated Making Capacity
    140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 1100 A 440 V power circuit IEC 60947
  • Control Circuit Voltage Limits
    0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC 0.85...1.1 Uc -40…131 °F (-40…55 °C) operational DC 1...1.1 Uc 131…158 °F (55…70 °C) operational DC
  • Connections - Terminals
    Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit bars 1 3 x 16 mm Power circuit lugs-ring terminals 0.67 in (17 mm))
  • Associated Fuse Rating
    10 A gG signalling circuit IEC 60947-5-1 200 A gG <= 690 V type 1 power circuit 160 A gG <= 690 V type 2 power circuit
  • Utilisation Category
    AC-3 AC-4 AC-1
  • Auxiliary Contacts Type
    Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • [Ie] Rated Operational Current
    125 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 80 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
  • [Ue] Rated Operational Voltage
    Power circuit <= 300 V DC 25...400 Hz Power circuit <= 690 V AC
  • Contactor Application
    Resistive load Motor control
  • [Ith] Conventional Free Air Thermal Current
    10 A 140 °F (60 °C) signalling circuit 125 A 140 °F (60 °C) power circuit
  • Mounting Support
    Rail Plate
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Non-Overlap Time
    1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • Operating Time
    95...130 ms closing 20...35 ms opening
  • Electrical Durability
    0.8 Mcycles 125 A AC-1 <= 440 V 1.5 Mcycles 80 A AC-3 <= 440 V
  • Power Dissipation Per Pole
    5.1 W AC-3 12.5 W AC-1
  • Minimum Switching Current
    5 mA signalling circuit
  • Hold-In Power Consumption In W
    22 W 68 °F (20 °C)
  • Inrush Power In W
    22 W 68 °F (20 °C))
  • Coil Technology
    Without built-in suppressor module
  • Time Constant
    75 ms
  • Insulation Resistance
    > 10 MOhm signalling circuit
  • Minimum Switching Voltage
    17 V signalling circuit
  • Signalling Circuit Frequency
    25...400 Hz
  • Maximum Operating Rate
    3600 cyc/h 140 °F (60 °C)
  • Mechanical Durability
    75 Mcycles
  • Front Cover
    With
  • Average Impedance
    0.8 mOhm - Ith 125 A 50 Hz power circuit
  • Rated Breaking Capacity
    1100 A 440 V power circuit IEC 60947
  • Control Circuit Type
    DC standard
  • Overvoltage Category
    III
  • [Uimp] Rated Impulse Withstand Voltage
    8 kV IEC 60947
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • [Uc] Control Circuit Voltage
    24 V DC
  • Device Short Name
    LC1D
  • Power Pole Contact Composition
    3 NO
  • Poles Description
    3P
  • Range
    TeSys
  • Product Or Component Type
    Contactor
  • Product Name
    TeSys D

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



1-year warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Schneider Electric

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Schneider Electric Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Schneider Electric Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Schneider Electric, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo