1104868 Phoenix Contact Electrical Safety Devices
Part#:1104868
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 1
Dec 23, 2024
Safe extension module with 4 safe outputs (0.4 A), 4 reset inputs, 4 signal outputs, TBUS interface, up to SILCL 3, Cat. 4/PL e, SIL 3, pluggable Push-in terminal block, TBUS connector included
About the manufacturer: Phoenix Contact is one of the manufacturers that offers Electrical Safety Devices that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 1104868 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Height 107.74 mm
- Designation Air clearances and creepage distances between the power circuits
- Protective circuit Serial protection against polarity reversal
- Number of inputs 4
- Max. permissible overall conductor resistance 1.2 kΩ (Input and reset circuit at US)
- Limiting continuous current 100 mA (per channel)
- Output voltage when switched off max. 0.1 V
- Test pulses < 80 µs (Test pulse width of low test pulses)
- Depth 113.6 mm
- Maximum altitude ≤ 2000 m (Above sea level)
- Power consumption at US typ. 0.72 W (Outputs inactive)
- Input voltage range "0" signal 0 V DC ... 5 V DC
- Current consumption typ. 10 mA (typically with US)
- Output description PNP, IEC 61131-2 Typ 0,1
- Leakage current max. 100 µA
- Discharging circuit Yes, internal
- Maximum inrush current 1.1 A (Δt = 3 s at Us)
- Nominal operating mode 100% operating factor
- Assembly instructions Observe derating
- Status display 1 x LED (green), 2 x LED (orange)
- Operating voltage display 1 x green LED
- Stop category 0
- Ambient temperature (operation) -10 °C ... 55 °C (observe derating)
- Rated control circuit supply voltage US 24 V DC -20 % / +20 % (provide external protection, typically 5 A)
- Filter time 250 ms ±2 ms (Test pulse rate > 500 ms)
- Input current range "0" signal < 1 mA
- Protective circuit/component Suppressor diode
- Nominal output voltage 24 V DC (Supply via A1)
- Max. inductive load max. 1.4 mH
- Max. capacitive load max. 680 nF
- Response time see user manual
- Mounting position vertical or horizontal
- Net weight 141 g
- Connection method Push-in connection
- Conductor cross-section AWG 24 ... 16
- Performance level (PL) e (2-channel wiring)
- Degree of pollution 2
- ECLASS 10.0.1 27371819
- China RoHS Environmentally friendly use period: unlimited = EFUP-e
- Ambient temperature (storage/transport) -20 °C ... 85 °C
- Max. permissible relative humidity (operation) 95 % (non-condensing)
- Inrush current max. 750 mA (Δt 1 s)
- Input name Reset inputs
- Input voltage range "1" signal 11 V DC ... 28.8 V DC
- Output name O1A, O1B, O2A, O2B, O3A, O3B, O4A, O4B
- Nominal output voltage range 18 V DC ... 27.6 V DC (US - 1.2 V)
- Ohmic load min. 50 Ω (Observe limiting continuous current)
- Short-circuit protection Yes (self-limitation at 1.1 A)
- Restart time min. 5 s (Boot time)
- Cycle time see user manual
- Min. degree of protection of inst. location IP54
- Housing material Polyamide PA non-reinforced
- Conductor cross section solid 0.2 mm² ... 2.5 mm²
- Stripping length 10 mm
- Standards/regulations EN 50178
- ECLASS 11.0 27371819
- Width 22.61 mm
- Max. permissible humidity (storage/transport) 95 % (non-condensing)
- Rated control supply current IS See supply A1/A2
- Description Output supply, connected internally to A1/A2
- Description of the input IEC 61131-2 type 3
- Cable length max. 100 m (per output)
- Number of outputs 4
- Switching frequency max. 1/4 x tCycle [Hz]
- Error detection time at 1-channel structure < 3.5 s (OFF state)
- Output voltage range 18.2 V DC ... 27.8 V DC (US - 1 V)
- Degree of protection IP20
- Housing color yellow
- pluggable Yes
- Rated insulation voltage 250 V AC
- Overvoltage category II
- Shock 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction)
- Voltage 24 V DC (via A1)
- Mounting type DIN rail mounting
- Protection class III (EN 50178)
- Indication 2 x LED (red)
- Conductor cross section flexible 0.2 mm² ... 2.5 mm²
- Safety Integrity Level (SIL) 2
- Safety Integrity Level Claim Limit (SIL CL) 3 (2-channel wiring)
- Vibration (operation) 10 Hz ... 150 Hz, 2g
- ECLASS 9.0 27371819
- Rated surge voltage/insulation Basic insulation 4 kV between 24 V power supply and I/Os to the housing
- Conformance CE-compliant
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$533.46
Stock:
1
Select Qty:
$533.46
$533.46 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨