X20SL8100 B&R Electronic Components

B&R X20SL8100 X20 SafeLOGIC, safety controller, openSAFETY gateway, removable application memory: SafeKEY, 1 POWERLINK interface, controlled node, integrated 2-port hub, including power supply module, 1x terminal block X20TB52 and X20 end cover plate X20AC0SR1 (right)
B&R

Part#:X20SL8100

Manufacturer:B&R

Product Lifecycle:Active

In-stock parts: 1

Dec 23, 2024

X20 SafeLOGIC, safety controller, openSAFETY gateway, removable application memory: SafeKEY, 1 POWERLINK interface, controlled node, integrated 2-port hub, including power supply module, 1x terminal block X20TB52 and X20 end cover plate X20AC0SR1 (right)

Check out the X20SL8100 B&R price in the box on the right side or send a quick quote.

Product Details

  • Weight190 g
  • Temperature Operation Vertical mounting orientation
    0 to 45°C
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. number of data points for each direction UINT
    16
  • Temperature Operation Horizontal mounting orientation
    0 to 60°C
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. number of data points for each direction UDINT
    16
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. number of data points for each direction INT
    16
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. number of data points for each direction DINT
    16
  • Data exchange between CPU and SafeLOGIC controller Max. number of data points for each direction DINT
    64
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. number of data points for each direction BOOL
    128
  • Data exchange between CPU and SafeLOGIC controller Max. number of data points for each direction UINT
    128
  • Data exchange between CPU and SafeLOGIC controller Max. number of data points for each direction BOOL
    1024
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd Module
    <1*10-10
  • Data exchange between CPU and SafeLOGIC controller Max. number of data points for each direction UDINT
    64
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wireless
    <1*10-14 * Number of openSAFETY packets per hour
  • Data exchange between CPU and SafeLOGIC controller Max. number of data points for each direction INT
    128
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wired
    Negligible
  • Dimensions Depth
    75 mm
  • Dimensions Height
    99 mm
  • Relative humidity Storage
    5 to 95%, non-condensing
  • Dimensions Width
    62.5+0.2 mm
  • Relative humidity Transport
    5 to 95%, non-condensing
  • Relative humidity Operation
    5 to 95%, non-condensing
  • Temperature Transport
    -40 to 85°C
  • Temperature Derating
    -
  • Temperature Storage
    -40 to 85°C
  • Min. cycle time Fieldbus
    200 µs
  • Mounting orientation Horizontal
    Yes
  • Mounting orientation Vertical
    Yes
  • Transfer Auto-MDI/MDIX
    Yes
  • Transfer Autonegotiation
    Yes
  • Transfer Full-duplex
    No
  • Transfer Physical layer
    100BASE-TX
  • Transfer Half-duplex
    Yes
  • Additional SafeDESIGNER limit values Max. number of variable with variable status
    1023
  • Additional SafeDESIGNER limit values Max. number of force variables
    64
  • Max. resources available for SafeDESIGNER info window entries Marker count
    16,382
  • Additional SafeDESIGNER limit values Max. number of function block types
    512
  • Max. resources available for SafeDESIGNER info window entries Memory for standard output data
    1024 bytes
  • Max. resources available for SafeDESIGNER info window entries Memory for safe input data
    6144 bytes
  • Max. resources available for SafeDESIGNER info window entries Memory for standard input data
    1024 bytes
  • Max. resources available for SafeDESIGNER info window entries Memory for safe output data
    2048 bytes
  • Max. resources available for SafeDESIGNER info window entries Marker memory
    262,144 bytes
  • Max. resources available for SafeDESIGNER info window entries Stack memory
    32,768 bytes
  • Max. resources available for SafeDESIGNER info window entries FB instances
    4096
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. number of linked Managing SafeDOMAINs
    Starting with mapp Safety 5.10.0 and hardware upgrade 2.2.1.0: 10
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. total number of data points for each direction
    16
  • Data exchange between SafeDOMAIN and SafeDOMAIN Max. total data width for each direction
    64 bytes
  • Data exchange between SafeDOMAIN and SafeDOMAIN Use as Connected SafeDOMAIN
    Yes, starting with mapp Safety 5.10.0 and hardware upgrade 2.2.1.0
  • Data exchange between CPU and SafeLOGIC controller Max. total data width for each direction
    512 bytes
  • Support for Safe Commissioning Options DINT
    64
  • Data exchange between SafeDOMAIN and SafeDOMAIN Use as Managing SafeDOMAIN
    Yes, starting with mapp Safety 5.10.0 and hardware upgrade 2.2.1.0
  • Support for Safe Commissioning Options UDINT
    64
  • Support for Safe Commissioning Options INT
    64
  • Support for Safe Commissioning Options UINT
    64
  • Support for Safe Commissioning Options BOOL
    512
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SFF
    >90%
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD
    <2*10-5
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 Proof test interval (PT)
    20 years
  • EN ISO 13849-1:2015 Mission time
    Max. 20 years
  • IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SIL CL
    SIL 3
  • EN ISO 13849-1:2015 MTTFD
    2500 years
  • Certifications KR
    Yes
  • EN ISO 13849-1:2015 Category
    Cat. 4
  • Certifications EAC
    Yes
  • Certifications ABS
    Yes
  • EN ISO 13849-1:2015 DC
    >94%
  • EN ISO 13849-1:2015 PL
    PL e
  • Certifications LR
    ENV1
  • Certifications ATEX
    Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
  • Certifications HazLoc
    cCSAus 244665; Process control equipment; for hazardous locations; Class I, Division 2, Groups ABCD, T5
  • Certifications UL
    cULus E115267; Industrial control equipment
  • Certifications DNV
    Temperature: A (0 - 45°C); Humidity: B (up to 100%); Vibration: A (0.7 g); EMC: B (bridge and open deck)
  • Certifications Functional safety
    cULus FSPC E361559; Energy and industrial systems; Certified for functional safety; ANSI UL 1998:2013
  • Diagnostics POWERLINK
    Yes, using LED status indicator
  • Diagnostics SafeKEY
    Yes, using LED status indicator
  • Certifications UKCA
    Yes
  • Diagnostics CPU function
    Yes, using LED status indicator
  • Certifications CE
    Yes
  • System requirements mapp Technology Package
    mapp Safety 5.7.0 or later
  • System requirements Safety Release
    1.7 or later
  • System requirements Automation Studio
    4.0.16 or later
  • System requirements Automation Runtime
    V3.08 or later (for AsSafety library F4.06 or later)
  • System requirements SafeDESIGNER
    3.1.0 or later
  • Note
    Order SafeKEY and SafeLOGIC range of functions using the X20MK configurator.; X20 end cover plate (right) included in delivery; 12-pin X20 terminal block, safety-keyed, included in delivery; SafeKEY cover included in delivery
  • Degree of protection per EN 60529
    IP20
  • Installation elevation above sea level
    0 to 2000 m, no limitation
  • Transfer rate
    100 Mbit/s
  • Type
    Type 3
  • Input current
    Max. 0.25 A
  • Line length
    Max. 100 m between 2 nodes (segment length)
  • Reverse polarity protection
    Yes
  • Variant
    2x shielded RJ45 port (hub)
  • Fieldbus
    POWERLINK controlled node
  • Input voltage
    24 VDC -15% / +20%
  • Timing precision
    Time * 0.05 + Cycle time of the safety application
  • Shortest task class cycle time
    1 ms
  • Max. number of SafeNODEs
    100, depends on the number of available operating licenses on the SafeKEY
  • Max. number of POWERLINK controlled nodes
    50
  • Power consumption
    4.3 W
  • B&R ID code
    0xDD61
  • System module
    CPU
  • SafeMOTION support
    Yes, depends on the number of available operating licenses on the SafeKEY
  • Cooling
    Fanless
  • Interfaces
    POWERLINK
  • Communication with each other
    Yes
  • Status indicators
    CPU function, POWERLINK, SafeKEY
  • Max. number of SafeMOTION axes
    70, depends on the data width of the modules used

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging



1-year warranty

Get a quick Quote!

Request a quote, and we will send you price within minutes.

Stock:

1

Select Qty:

Average response time: 11 minutes

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of B&R

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

B&R Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many B&R Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from B&R, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo