X20SO6530 B&R Electronic Components
Part#:X20SO6530
Manufacturer:B&R
Product Lifecycle:Active
In-stock parts: 3
Dec 23, 2024
X20 safe digital output module, 6 relays with 1 normally open contact each, 230 VAC / 6 A, 24 VDC / 6 A
Check out the X20SO6530 B&R price in the box on the right side or send a quick quote.
Product Details
- Safe relay channels EN ISO 13849-1:2015 Category Cat. 1 if the relay channel is used individually, ; Cat. 4 if 2 relay channels are connected in series
- Temperature Operation Horizontal mounting orientation 0 to 60°C
- Temperature Operation Vertical mounting orientation 0 to 50°C
- Safe relay channels IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 SIL CL SIL 1 if the relay channel is used individually,; SIL 3 if 2 relay channels are connected in series
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd openSAFETY wired Negligible
- Safe relay channels EN ISO 13849-1:2015 PL PL c if the relay channel is used individually,; PL e if 2 relay channels are connected in series
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFH / PFHd Per channel <1*10-10
- Relative humidity Storage 5 to 95%, non-condensing
- Certifications Relays EN 50205 Yes
- Certifications Relays EN 50155 No
- Relative humidity Transport 5 to 95%, non-condensing
- Temperature Transport -40 to 85°C
- Relative humidity Operation 5 to 95%, non-condensing
- Temperature Storage -40 to 85°C
- Temperature Derating See section "Derating".
- Mounting orientation Vertical Yes
- Mounting orientation Horizontal Yes
- Max. switching capacity UL 508 B300 / R300
- Max. switching capacity DC1 24 VDC / 6 A
- Max. switching capacity DC13 24 VDC / 4 A / 0.1 Hz
- Max. switching capacity AC15 230 VAC / 5 A
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 Proof test interval (PT) 20 years
- Switching delay 0 → 1 <50 ms
- Switching delay 1 → 0 <50 ms; Hardware upgrade 2.2.0.0 or later: <20 ms
- Max. switching capacity AC1 230 VAC / 6 A
- IEC 61508:2010,; IEC 61511:2004,; EN 62061:2013 PFD <2*10-5
- Certifications UL cULus E115267; Industrial control equipment
- Certifications UKCA Yes
- Certifications CE Yes
- Certifications DNV In preparation
- EN ISO 13849-1:2015 Mission time Max. 20 years
- Certifications ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
- Certifications EAC Yes
- EN ISO 13849-1:2015 MTTFD 2500 years
- Certifications Functional safety cULus FSPC E361559; Energy and industrial systems; Certified for functional safety; ANSI UL 1998:2013
- Electrical isolation Channel - Channel Yes
- Blackout mode Function Module functionality
- Power consumption Internal I/O 1.65 W
- Electrical isolation Channel - Bus Yes
- Power consumption Bus 0.26 W
- Blackout mode Scope Module
- System requirements mapp Technology Package mapp Safety 5.7.0 or later
- Blackout mode Standalone mode No
- Diagnostics Module run/error Yes, using LED status indicator and software
- Diagnostics Outputs Yes, using LED status indicator and software
- System requirements Safety Release 1.10 or later
- System requirements SafeDESIGNER 4.2.0 or later
- System requirements Automation Runtime 4.2 or later
- System requirements Automation Studio 4.2.5 or later
- Pitch 25+0.2 mm
- Degree of protection per EN 60529 IP20
- Note Order 1x safety-keyed terminal block separately.; Order 1x safety-keyed bus module separately.
- Max. inrush current AC: 50 A for 100 ms, DC: 10 A for 200 ms
- Installation elevation above sea level 0 to 2000 m, no limitation
- Overvoltage category per EN 60664-1 II
- Nominal output current 5 mA to 6 A (hardware revision
- Short-circuit proof
Yes, 1000 A (with specified short-circuit/overload protection)- Coil voltage
24 VDC -15% / +20%- Contact resistance (without terminal block)
20 mΩ- Contact service life
See "Contact service life".- Short-circuit/Overload protection
External 6 A gL/gG fuse (melting fuse), LS automat C characteristic 1.6 A- Switching voltage range
5 to 24 VDC, 5 to 230 VAC- Diagnostic status
Contact position determined by positively driven contacts- Max. switching frequency
See section "Inrush current behavior for output channels".- Insulation voltage between channel and channel
Tested at 1350 VAC- Insulation voltage between channel and bus
Safe disconnection of 300 VAC per EN 50178- Variant
Relay / Normally open contact, internal high-side and low-side control- Integrated protection
Reverse polarity protection- Nominal voltage
24 VDC- Additional power dissipation caused by actuators (resistive) [W]
4.32- I/O module
6 relays with 1 normally open contact each, 230 VAC / 6 A, 24 VDC / 6 A- Quantity
6- B&R ID code
0xF22A- Max. I/O cycle time
1 ms- Status indicators
I/O function per channel, operating state, module status- Voltage range
24 VDC -15% / +20% - Short-circuit proof
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
Related documents X20SO6530 Specs
1-year warranty
Get a quick Quote!
Request a quote, and we will send you price within minutes.
Stock:
3
Select Qty:
Average response time: 11 minutes
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of B&R
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
B&R Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many B&R Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from B&R, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨