2904608 Phoenix Contact AC/DC Power Supplies
Part#:2904608
Manufacturer:Phoenix Contact
Product Lifecycle:Active
In-stock parts: 56
Dec 22, 2024
Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 1-phase, output: 12 V DC/15 A
About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.
Check out the 2904608 Phoenix Contact price in the box on the right side or send a quick quote.
Product Details
- Width 50 mm
- Depth with alternative assembly 53 mm
- Ambient temperature (start-up type tested) -40 °C
- Dielectric strength maximum 300 V AC 60 s
- Nominal power consumption 221 VA
- Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
- Nominal output voltage 12 V DC
- Dynamic Boost (IDyn.Boost) 20 A (5 s)
- Connection in series yes
- Net weight 1 kg
- Insulation voltage input/output 4 kV AC (type test)
- Connection method Push-in connection
- Stripping length 8 mm
- Standard - Electrical safety IEC 61010-2-201 (SELV)
- Standard – Safety extra-low voltage IEC 61010-1 (SELV)
- Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
- Harmonic currents EN 61000-3-2
- Frequency range 50 Hz ... 60 Hz
- Test field strength 110 A/m
- Signal 4 kV (Test Level 4 - asymmetrical)
- Voltage 2.5 kV
- Frequency 50 Hz
- Voltage dip 0 %
- Asymmetrical conducted disturbance variables EN 61000-4-16
- Test level 5 16.7 Hz 50 Hz 60 Hz (Test Level 4)
- Input, output (test level 2) 10 MHz
- Input, output (test level 1) 100 kHz 1 MHz (Test Level 3 - symmetrical)
- REACh SVHC Lead 7439-92-1
- ECLASS 9.0 27040701
- Height 130 mm
- Installation distance top/bottom 50 mm / 50 mm
- Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
- Degree of pollution 2
- Current consumption 2.4 A (100 V AC)
- Input fuse 8 A (slow-blow, internal)
- Protective circuit/component Varistor, gas-filled surge arrester
- Static Boost (IStat.Boost) 17.5 A
- Derating > 60 °C ... 70 °C (2.5%/K)
- Feedback voltage resistance ≤ 25 V DC
- Maximum power dissipation in no-load condition < 4 W (120 V AC)
- Efficiency typ. 91.2 % (120 V AC)
- Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
- Conductor cross section solid min. 0.2 mm²
- Conductor cross section flexible max. 1.5 mm²
- HART FSK Physical Layer Test Specification Compliance Output voltage UOut compliant
- Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1
- Mains variation/undervoltage SEMI F47-0706, EN 61000-4-11
- Conducted noise emission EN 55016
- Noise emission EN 55016
- Electromagnetic HF field EN 61000-4-3
- Comments Criterion A
- Additional text Test Level 2
- Test level 1 15 Hz 150 Hz (Test Level 4)
- Damped oscillating magnetic field EN 61000-4-10
- Test level 6 16.7 Hz 50 Hz 60 Hz (Test Level 4)
- Input, output (test level 3) 100 kHz 1 MHz (Test Level 3 - asymmetrical)
- Criterion A Normal operating behavior within the specified limits.
- ECLASS 10.0.1 27040701
- ETIM 7.0 EC002540
- Width with alternative assembly 122 mm
- Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Installation height ≤ 5000 m (> 2000 m, observe derating)
- AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
- Selective Fuse Breaking (ISFB) 60 A (15 ms)
- Residual ripple < 70 mVPP (with nominal values)
- Power loss nominal load max. < 18 W (120 V AC)
- Insulation voltage input / PE 3.5 kV AC (type test)
- Insulation voltage output / PE 0.5 kV DC (type test)
- Conductor cross section AWG min. 24
- EMC requirements for noise immunity EN 61000-6-1
- Standard - Safety of transformers EN 61558-2-16
- CSA CAN/CSA-C22.2 No. 60950-1-07
- Flicker EN 61000-3-3
- Fast transients (burst) EN 61000-4-4
- Output 0.5 V (Test Level 2 - symmetrical)
- I/O/S asymmetrical
- Number of periods 0,5 / 1 / 5 / 50 / 250 periods
- Test level 2 150 Hz 1.5 kHz (Test Level 4)
- Test level 3 1.5 kHz 15 kHz (Test Level 4)
- Signals (test level 1) 100 kHz 1 MHz (Test Level 3 - symmetrical)
- Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
- ECLASS 11.0 27040701
- Height with alternative assembly 130 mm
- Degree of protection IP20
- Ambient temperature (storage/transport) -40 °C ... 85 °C
- Nominal input voltage range 100 V AC ... 240 V AC
- Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
- Inrush current typ. 15 A (at 25 °C)
- Control deviation < 0.5 % (Static load change 10 % ... 90 %)
- Environmental protection directive RoHS Directive 2011/65/EU
- Protection class I
- Conductor cross section flexible min. 0.2 mm²
- EMC requirements for noise emission EN 61000-6-3
- Rail applications EN 50121-3-2
- Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
- Electrostatic discharge EN 61000-4-2
- Input 2 kV (Test Level 4 - symmetrical)
- Power frequency magnetic field EN 61000-4-8
- Pulse-shape magnetic field EN 61000-4-9
- Test level 4 15 kHz 150 kHz (Test Level 4)
- Attenuated oscillating wave EN 61000-4-18
- Signals (test level 2) 100 kHz 1 MHz (Test Level 3 - asymmetrical)
- Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
- China RoHS Environmentally Friendly Use Period = 25;
- Depth 125 mm
- Installation distance right/left 5 mm / 5 mm
- Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
- Climatic class 3K3 (in acc. with EN 60721)
- Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
- Discharge current to PE < 3.5 mA
- Mains buffering time typ. 55 ms (120 V AC)
- Type of protection Transient surge protection
- Setting range of the output voltage (USet) 12 V DC ... 15 V DC (constant capacity)
- Nominal output current (IN) 15 A
- Connection in parallel Yes, for redundancy and increased capacity
- Protection against overvoltage at the output (OVP) ≤ 18 V DC
- Output power 180 W
- Typical response time 300 ms (from SLEEP MODE)
- MTBF (IEC 61709, SN 29500) > 1196000 h (25 °C)
- Mounting position horizontal DIN rail NS 35, EN 60715
- Conductor cross section solid max. 1 mm²
- Conductor cross section AWG max. 16
- EMC requirements, power plant IEC 61850-3
- Standard - Safe isolation IEC 61558-2-16
- Standard – Limitation of mains harmonic currents EN 61000-3-2
- UL approvals UL Listed UL 508
- Discharge in air 15 kV (Test Level 4)
- Contact discharge 8 kV (Test Level 4)
- Conducted interference EN 61000-4-6
- Voltage dips EN 61000-4-11
- Attenuated sinusoidal oscillations (ring wave) EN 61000-4-12
- ETIM 6.0 EC002540
Product condition
ORIGINAL PACKAGING
SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging
This item can ship within 24h!
1-year warranty
$328.43
Stock:
56
Select Qty:
$328.43
$328.43 each
By purchasing this item, you agree to the Terms & Conditions
Quotebeam is NOT an authorized distributor of Phoenix Contact
Shipping and Delivery Worldwide
calculate costs and time
Secure Payment Processing
with money back guarantee
1 year warranty
on all parts
Responsive Customer Support
we're here to help!
Need more details?
Feel free to chat with us or check our FAQ
Phoenix Contact Disclaimer:
The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.
Relevant products
Do you have questions?
We’re here for you ✨