Bryan Obida

Live support:

Monday - Friday 6AM - 6PM PST

2904620 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2904620 Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/5 A
Phoenix Contact

Part#:2904620

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 30

Dec 22, 2024

Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 3-phase, output: 24 V DC/5 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2904620 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Height with alternative assembly
    130 mm
  • Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
  • Installation height
    ≤ 5000 m (> 2000 m, observe derating)
  • Frequency range (fN)
    50 Hz ... 60 Hz -10 % ... +10 %
  • Mains buffering time
    typ. 34 ms (3x 400 V AC)
  • Setting range of the output voltage (USet)
    24 V DC ... 29.5 V DC (constant capacity)
  • Derating
    > 60 °C ... 70 °C (2.5%/K)
  • Residual ripple
    < 30 mVPP (with nominal values)
  • Environmental protection directive
    RoHS Directive 2011/65/EU
  • MTBF (IEC 61709, SN 29500)
    > 1560000 h (25 °C)
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section AWG max.
    16
  • EMC requirements for noise immunity
    EN 61000-6-1
  • HART FSK Physical Layer Test Specification Compliance
    Output voltage UOut compliant
  • Standard - Safe isolation
    IEC 61558-2-16 pending
  • SIQ
    BG (type approved)
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • DNV GL conducted interference
    Class A
  • Flicker
    EN 61000-3-3
  • Contact discharge
    8 kV (Test Level 4)
  • Test field strength
    110 A/m
  • Conducted interference
    EN 61000-4-6
  • Number of periods
    0,5 / 1 / 5 / 50 / 250 periods
  • Attenuated sinusoidal oscillations (ring wave)
    EN 61000-4-12
  • Height
    130 mm
  • Installation distance right/left
    5 mm / 5 mm
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Degree of pollution
    2
  • AC frequency range
    50 Hz ... 60 Hz -10 % ... +10 %
  • Nominal power consumption
    283 VA
  • Recommended breaker for input protection
    3x 6 A (Characteristic B, C or comparable)
  • Nominal output voltage
    24 V DC
  • Static Boost (IStat.Boost)
    6.25 A
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Power loss nominal load max.
    < 15 W (400 V AC)
  • Insulation voltage input / PE
    3.5 kV AC (type test)
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • Conductor cross section solid max.
    1 mm²
  • Stripping length
    8 mm
  • Standard - Electrical safety
    IEC 61010-2-201 (SELV)
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Rail applications
    EN 50121-3-2
  • CSA
    CAN/CSA-C22.2 No. 60950-1-07
  • Conducted noise emission
    EN 55016
  • Electrostatic discharge
    EN 61000-4-2
  • Discharge in air
    15 kV (Test Level 4)
  • Frequency range
    50 Hz ... 60 Hz
  • Output
    1 kV (Test Level 3 - symmetrical)
  • Power frequency magnetic field
    EN 61000-4-8
  • Pulse-shape magnetic field
    EN 61000-4-9
  • Asymmetrical conducted disturbance variables
    EN 61000-4-16
  • Test level 5
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Signals (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • ECLASS 11.0
    27040701
  • ECLASS 9.0
    27040701
  • ETIM 6.0
    EC002540
  • Depth
    125 mm
  • Installation distance top/bottom
    50 mm / 50 mm
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Input voltage range
    3x 400 V AC ... 500 V AC -20 % ... +10 %
  • Input fuse
    2 A (slow-blow, internal)
  • Protective circuit/component
    Varistor, gas-filled surge arrester
  • Selective Fuse Breaking (ISFB)
    30 A (15 ms)
  • Control deviation
    < 0.5 % (Static load change 10 % ... 90 %)
  • Typical response time
    300 ms (from SLEEP MODE)
  • Insulation voltage input/output
    4 kV AC (type test)
  • Connection method
    Push-in connection
  • Conductor cross section AWG min.
    24
  • Standard – Safety extra-low voltage
    IEC 61010-1 (SELV)
  • Standard - power supply devices for low voltage with DC output
    EN 61204-3
  • Mains variation/undervoltage
    SEMI F47-0706, EN 61000-4-11
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Noise emission
    EN 55016
  • Additional text
    Test Level 2
  • Electromagnetic HF field
    EN 61000-4-3
  • Fast transients (burst)
    EN 61000-4-4
  • Surge voltage load (surge)
    EN 61000-4-5
  • Voltage
    2.5 kV
  • Voltage dip
    0 %
  • Test level 4
    15 kHz 150 kHz (Test Level 4)
  • Signals (test level 2)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • ECLASS 10.0.1
    27040701
  • UNSPSC 21.0
    39121004
  • Width
    36 mm
  • Depth with alternative assembly
    39 mm
  • Ambient temperature (start-up type tested)
    -40 °C
  • Nominal input voltage range
    3x 400 V AC ... 500 V AC
  • Current consumption
    3x 0.53 A (400 V AC)
  • Inrush current
    typ. 11 A (at 25 °C)
  • Type of protection
    Transient surge protection
  • Nominal output current (IN)
    5 A
  • Connection in series
    yes
  • Feedback voltage resistance
    ≤ 35 V DC
  • Output power
    120 W
  • Net weight
    0.6 kg
  • Insulation voltage output / PE
    0.5 kV DC (type test)
  • Conductor cross section flexible max.
    1.5 mm²
  • EMC requirements, power plant
    IEC 61850-3
  • Frequency
    50 Hz
  • Damped oscillating magnetic field
    EN 61000-4-10
  • Attenuated oscillating wave
    EN 61000-4-18
  • Input, output (test level 1)
    100 kHz 1 MHz (Test Level 3 - symmetrical)
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 5.1
    27242213
  • UNSPSC 20.0
    39121004
  • Width with alternative assembly
    122 mm
  • Degree of protection
    IP20
  • Nominal input voltage
    3 V
  • Discharge current to PE
    < 3.5 mA
  • Power factor (cos phi)
    0.48
  • Dynamic Boost (IDyn.Boost)
    10 A (5 s)
  • Protection against overvoltage at the output (OVP)
    ≤ 32 V DC
  • Maximum power dissipation in no-load condition
    < 3 W (400 V AC)
  • Efficiency
    typ. 89 % (400 V AC)
  • Protection class
    I
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section flexible min.
    0.2 mm²
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard - Safety of transformers
    IEC 61558-2-16 pending
  • Standard - safety for equipment for measurement, control, and laboratory use
    IEC 61010-1
  • UL approvals
    UL Listed UL 508
  • Shipbuilding approval
    DNV GL, PRS, BV, LR, ABS
  • Harmonic currents
    EN 61000-3-2
  • DNV GL noise radiation
    Class B
  • Comments
    Criterion A
  • Input
    3 kV (Test Level 4 - symmetrical)
  • Signal
    1 kV (Test Level 2 - asymmetrical)
  • I/O/S
    asymmetrical
  • Voltage dips
    EN 61000-4-11
  • Test level 1
    15 Hz 150 Hz (Test Level 4)
  • Test level 3
    1.5 kHz 15 kHz (Test Level 4)
  • Test level 6
    16.7 Hz 50 Hz 60 Hz (Test Level 4)
  • Criterion A
    Normal operating behavior within the specified limits.
  • REACh SVHC
    Lead 7439-92-1
  • UNSPSC 18.0
    39121004
  • Test level 2
    150 Hz 1.5 kHz (Test Level 4)
  • Input, output (test level 2)
    10 MHz
  • Input, output (test level 3)
    100 kHz 1 MHz (Test Level 3 - asymmetrical)
  • Criterion C
    Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
  • ECLASS 6.0
    27049005
  • UNSPSC 13.2
    39121004
  • UNSPSC 19.0
    39121004

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$247.13

Stock:

30

Select Qty:

$247.13

$247.13 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo